New ABB Contactor AX80-30-00-84 3-Phase Motor and Circuit Control Up to 690 VAC

$ 158.4

Availability: 100 in stock
  • Condition: New
  • MPN: AX80-30-00-84
  • Refund will be given as: Money back or replacement (buyer's choice)
  • Item must be returned within: 30 Days
  • Return shipping will be paid by: Seller
  • Restocking Fee: No
  • All returns accepted: Returns Accepted
  • Brand: ABB

    Description

    New ABB Contactor AX80-30-00-84 is mainly used for controlling 3-phase motors and powers circuits up to 690 VAC.
    *Block type design
    *3 main poles
    *AC operated
    *Optional auxiliary contact blocks may be added
    UNSPSC:
    39121529
    IDEA Granular Category Code (IGCC):
    4755 >> Contactors
    General Use Rating UL/CSA:
    (600 V AC) 105 A
    Horsepower Rating UL/CSA:
    (120 V AC) Single Phase 7-1/2 Hp
    (240 V AC) Single Phase 15 Hp
    (200 ... 208 V AC) Three Phase 25 Hp
    (220 ... 240 V AC) Three Phase 30 Hp
    (440 ... 480 V AC) Three Phase 60 Hp
    (550 ... 600 V AC) Three Phase 75 Hp
    Tightening Torque UL/CSA:
    Auxiliary Circuit 9 in·lb
    Control Circuit 9 in·lb
    Main Circuit 35 in·lb
    Environmental
    Ambient Air Temperature:
    Close to Contactor for Storage -60 ... +80 °C
    Close to Contactor Fitted with Thermal O/L Relay -25 ... +55 °C
    Close to Contactor without Thermal O/L Relay -40 ... +70 °C
    Near Contactor for Operation in Free Air -40 ... +70 °C
    Climatic Withstand:
    acc. to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 specification II
    Maximum Operating Altitude Permissible:
    3000 m
    RoHS Status:
    Following EU Directive 2002/95/EC August 18, 2005 and amendment
    Technical
    Number of Main Contacts NO:
    3
    Rated Operational Voltage:
    Auxiliary Circuit 690 V
    Main Circuit 690 V
    Rated Frequency (f):
    Auxiliary Circuit 50 / 60 Hz
    Main Circuit 50 / 60 Hz
    Conventional Free-air Thermal Current (I
    th
    ):
    acc. to IEC 60947-4-1, Open Contactors q = 40 °C 125 A
    Rated Operational Current AC-1 (I
    e
    ):
    (690 V) 40 °C 125 A
    (690 V) 70 °C 85 A
    (220 / 240 V) 55 °C 105 A
    Rated Operational Current AC-3 (I
    e
    ):
    (220 / 230 / 240 V) 55 °C 80 A
    (380 / 400 V) 55 °C 80 A
    (415 V) 55 °C 80 A
    (440 V) 55 °C 70 A
    (500 V) 55 °C 65 A
    (690 V) 55 °C 46 A
    Rated Operational Power AC-3 (P
    e
    ):
    (220 / 230 / 240 V) 22 kW
    (380 / 400 V) 37 kW
    (415 V) 40 kW
    (440 V) 40 kW
    (500 V) 45 kW
    (690 V) 40 kW
    Rated Short-time Withstand Current (I
    cw
    ):
    at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 650 A
    at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 135 A
    at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 250 A
    at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1000 A
    at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 370 A
    for 1 s -empty- A
    Maximum Breaking Capacity:
    cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 1300 A
    cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 630 A
    Maximum Electrical Switching Frequency:
    AC-1 600 cycles per hour
    AC-3 600 cycles per hour
    Rated Insulation Voltage (U
    i
    ):
    acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 V
    Rated Impulse Withstand Voltage (U
    imp
    ):
    6 kV
    Maximum Mechanical Switching Frequency:
    3600 cycles per hour
    Rated Control Circuit Voltage (U
    c
    ):
    50 Hz 110 V
    60 Hz 110 ... 120 V